中圖分類號:TU745 文獻標志碼:A 文章編號:2095-2945(2025)24-0082-07
Abstract:The hydration heatof massconcrete pouring causes theinternal heatingandcoling processIfreasonable measures arenottaken,harmfultemperatureshrinkagecrackswillappearuringthemassconcretepouringandcoolingprocessTetraditioal practiceofsetingpost-pouredstripshasgreatdificultiesitermsofshedule,qualityandmanagementInviewoftissituation thispapertakesthefoundationslabpouringofahigh-risebuildingwithatotalbuildingareaof178,50Om2astheresearch background,itroducestchicalicipleofempingiletdndtdingsilethod,dfti processofthejumpingsilomethodconstructiontechnologyinactualprojectslabpouringandkeyconstructiontechnicaleasures. Basedonthefiniteelementcalculationresults,therationalityofthejumpingsilomethodconstructionforthisprojectisproved, which providesengineering practical experience forthejumping silo method pouring construction technologyof mass concrete.
Keywords:massconcrete;jumpingmethodconstructiontechnology;thermal stress finiteelementanalysis;concreteexpansion post-poured strip; technical application
混凝土材料抗拉強度通常僅為抗壓強度的十分之一,短期加載極限拉伸變形范圍為 (0.6~1.0)×10-4 大約相當于溫降 6~10C[1] 。相較普通鋼筋混凝土結構,大體積混凝土配筋率較低,混凝土部分承擔較大部分拉伸變形,鋼筋承受受拉變形作用不突出,易出現受拉裂縫。大體積混凝土澆筑初期水泥水化熱導致混凝土內部溫度急劇上升,混凝土強度尚未完全成型,保留一定“流塑性”,升溫變形引起的壓應力較?。凰療岷笃谏郎厮俣刃∮谏崴俣?,混凝土內部溫度逐漸降低,混凝土強度和彈性模量成型,混凝土降溫收縮變形將產生較大拉應力,引起開裂。上述過程基于混凝土較低的熱傳導性能,混凝土溫升溫降過程在內部產生溫度梯度,因此在大體積混凝王施工過程中,采取合理措施減少和釋放溫度應力是研究重點。
1 工程概況
余政工出(2020)32號軟件和信息技術服務項目位于市余杭區五常街道,總建筑面積 178500m2 是由一棟十字形主樓和地下室組成的高層建筑,地上10層,地下4層,如圖1所示。地上主樓采用框架-剪力墻結構,地下室采用板柱結構,基礎采用樁筏式基礎。地下室長 167.8m ,寬 143.6m ,地下工程防水等級為一級,基礎及地下室外墻混凝土設計抗滲等級為P6~P8,底板厚度 1.2m ,底板采用跳倉法施工,施工現場底板澆筑如圖2所示。
2 跳倉法施工技術
2.1大體積混凝土施工溫度效應
跳倉法是解決大體積混凝土施工溫度裂縫的一種施工方法,可替代傳統設置后澆帶施工方法,具體做法為將大體積混凝土劃分為多個倉塊,相鄰混凝土倉塊施工時間間隔控制大于7d,利用間隔時間釋放混凝土水化熱降溫收縮變形產生的約束應力?!?br>