摘 要:本文主要對廣州地區(qū)發(fā)生的一起110kV電纜瓷套終端漏油事件進(jìn)行分析。首先闡述這起事件發(fā)生的背景及具體缺陷,然后從工藝設(shè)計、施工質(zhì)量等方面分析漏油的原因,最后提出防止此類缺陷發(fā)生的建議,以期為相關(guān)學(xué)者的研究提供借鑒。
關(guān)鍵詞:瓷套終端;漏油;缺陷;原因
中圖分類號:TM755 文獻(xiàn)標(biāo)識碼:A 文章編號:1003-5168(2019)31-0126-04
Analysis and Treatment of the Cause of Oil Leakage
Defect in 110kV Cable Terminal
HE Wei LI Dingning XIAO Jianjian XU Yan
(Guangzhou Power Supply Bureau Co.,Ltd.,Guangzhou Guangdong 510310)
Abstract: This paper mainly analyzed the oil leakage of 110kV cable porcelain bushing terminal in Guangzhou. First of all, the background and specific defects of the incident were described. Then, the causes of oil leakage were analyzed from the aspects of process design and construction quality. Finally, suggestions were put forward to prevent such defects, in order to provide reference for the research of relevant scholars.
Keywords: bushing terminal;oil leakage;defect;causes
1 事件背景
2014年5月,電纜運行人員在日常巡視過程中發(fā)現(xiàn),110kV XX #39電纜終端塔頭A相電纜尾管部位發(fā)現(xiàn)有絕緣油滲漏情況(見圖1),且漏油量較大,尾管上方、電纜外護(hù)層上都是油跡。由此,工作人員推測瓷套終端的密封功能可能失效,瓷套管內(nèi)絕緣油大量流失,絕緣性能下降,已嚴(yán)重影響該瓷套終端的安全運行,因此必須盡快安排停電進(jìn)行消缺處理。發(fā)生事故的110kV電纜的基本資料如表1所示。
2 制訂初步處理方案
根據(jù)漏油情況,電纜運行班組制訂了初步檢修方案,
具體如下:①拆除缺陷相A相尾管,檢查漏油情況;②拆除三相上部金具,測量并記錄硅油表面距離套管頂部的尺寸,判斷其他兩相漏油情況;③移除故障相瓷套管,放干硅油,清潔現(xiàn)場環(huán)境和多余油跡;④核對關(guān)鍵部位尺寸,分析漏油原因;⑤對故障相進(jìn)行吊裝套管,倒入硅油,做好密封。
3 缺陷相分析
第一,打開尾管,發(fā)現(xiàn)尾管內(nèi)積累大量絕緣油(見圖2),并發(fā)現(xiàn)編織袋未能較好地焊接在鋁護(hù)套上(見圖3),存在假焊、漏焊現(xiàn)象(見圖4),因此使鋁護(hù)套上產(chǎn)生了電腐蝕(見圖5)。
第二,檢查密封底盤油嘴封帽,發(fā)現(xiàn)油嘴干燥,可見該處不是造成本次漏油的原因。……