Research on fault diagnosis and fault toleranttechnology of IGBT in active power filters

2015-03-09 03:32:24ChengGONGZhenxingLIUCuiLIKaiFENG
機(jī)床與液壓 2015年6期
關(guān)鍵詞:故障診斷科技故障

Cheng GONG,Zhen-xing LIU ,Cui LI,Kai FENG

(1 College of Information Science and Engineering,Wuhan University of Science and Technology,Wuhan 430081,China)

(2Wuhan University of Science and Technology Engineering Research Center of Metallurgical Automation and Detection Technique,Ministry of Education,Wuhan 430081,China)

Research on fault diagnosis and fault toleranttechnology of IGBT in active power filters

Cheng GONG1,2*,Zhen-xing LIU1,2,Cui LI1,2,Kai FENG1,2

(1College of Information Science and Engineering,Wuhan University of Science and Technology,Wuhan 430081,China)

(2Wuhan University of Science and Technology Engineering Research Center of Metallurgical Automation and Detection Technique,Ministry of Education,Wuhan 430081,China)

For the IGBT(Insulated Gate Bipolar Transisto)of active power filter is prone to failurewhichmay result in serious consequences,an idea of detecting and locating the breakdown of IGBT on basis of DSP software and a fault tolerant topology of redundant single bridge arm of active power filter are proposed in this paper.Following the analysis of the algorithm of fault diagnosis of open circuit,a fault tolerant topology of active power filter and a specific implementmethod of fault-tolerant control are provided.Meanwhile,a related simulation model of the control system of active power filter is established on the MATLAB/Simulink simulation platform where the feasibility of this control scheme is verified through simulation experiments.

Active power filter(APF),IGBT,Detecting fault through software,F(xiàn)ault tolerant control

*Corresponding author:Cheng GONG,Master graduate student.

E-mail:gc7223739@163.com

1 In troduction

With the dramatic increase of nonlinear load of power system,which ismainly represented by power electronic devices,problems concerning power quality in terms of voltage fluctuation,flicker and unbalanced,three-phase emerged.Active power filter(APF),basing on three-phase six-switch and being able to dynamically control the harmonic and reactive power compensation,has been widely used[1].

The power semiconductor devices-IGBT in the APF is themost prone to failure after work for a long time with high frequency and under high temperature condition.Yet how to improve its stability and reliability effectively remains a problem.At the same time,the stability and reliability of IGBT determines the reliability of APF,and any failure in IGBT will lead to a breakdown of the whole system,disastrous consequenceswill emerge atworst.In order to enhance the stability and reliability of the system,prolong the time of reliable operation of the APF and buy time for the maintenance of APF after the failure of IGBT APF,fault diagnosis and fault-tolerant control of APF has become a very important subject.With fault-tolerant control of APF being an emerging discipline,few domestic researches have been done on it.It shows good development prospects.In terms of fault-tolerant control of APF,what the domestic and foreign scholars usually do is to reconfigure.the circuit topology structure of active power after the happening of failure and provide a corresponding fault tolerant strategy tomaintain the stability of the system to recover the performance beforehand asmuch as possible[2-4].Literature[3]puts forward a kind of fault-tolerant active power filter on basis of the structure of three-phase four-switch inverter.With this kind of fault-tolerant topology structure,the only thing should be done after failure is to switch a switch,which helps a lot in cost savings.Buta switch of the control algorithm is necessary in the process of fault-tolerant control.Since the APF based on the three-phase four-switch control algorithm is not very perfect now,the compensation effect is no better than the original system.Literature[4]puts forward a kind of open circuit diagnosis and faulttolerant control scheme based on hardware circuit.

Based on the research of scholars both at home and abroad,this article puts forward a kind of IGBT open circuit faults in the detection of APF on basis of DSP software and a fault-tolerant APF control scheme of redundant single bridge arm.When fault in IGBT of APF occurs,the system locates the fault by DSP,removes the fault phase,access the redundant bridge arm into the system,and meanwhile,switches the control signals into the accessed redundant bridge arm.The fault-tolerant APF system,using software to test the location of fault in IGBT,is able to locate faults timely and accurately without the necessity of switching algorithm during the implementation of faulttolerant control.Besides,APF can stillmaintain stable operation,which improves the stability of the system reliability.

2 Analysis of IGBT fau lt detection m ethod based on softw are [5-7]

For the detection of open circuit fault of IGBT in the APF,most previous studies detected faults based on the hardware circuit ormade artificial analysis after gathering failure data from the field.The method of online detecting faults in IGBT on basis of software in the fault-tolerant control of APF has not been used yet.This paper proposes an idea of online detection of faults in IGBT based on DSP software,aiming to detect the location of IGBT failure timely on the basis of saving hardware cost.

The diagnosis of IGBT fault in the three-phase AC motor inverter can be done by current vector path chart.

Through Clarke transform,three-phase alternating current can be transformed into theα,β,static coordinates of two-phase alternating current(AC)iαand iβ.The transforming formula is as follow:i=i

As shown in Fig.1,after the drawing of the current vector diagram with iαand iβbeing the horizontal axis and vertical axis respectively,it can be seen that in the normal steady state,the graph of current vector is circular,the size of the circle is proportional to the load and the scope forφ is(-∞,+∞).

Fig.1 Current path chart under the norm al state

When IGBT open circuit fault occurs,the current vector trajectory has its characteristics.When open circuit fault occurs to T1~T6,the current vector trajectory of them are shown respectively in Fig.2.With the fault analysis of a phase as an example,when IGBT tube T1and T2in a phase respectively disconnects,the current vector diagram as shown in Fig.2(a),(b)will be got.After the T1is disconnected,the positive half cycle is lost in a phase current,and the ia=0 at thismoment.But since the fly-wheel diode which is in reverse parallelwith T1is able to go on the stream with T2,the negative half cycle is notaffected.So the current trajectory can be divided into two parts:When ia<0,the track remains the same,its shape is half arc,and φ∈(-∞,+∞);when ia=0,φ =0,and its shape is a straight line segment.

When T2is disconnected,the situation is the contrary.Without the negative half cycle in the a phase current,and since the fly-wheel diode which is in reverse parallel with T2is able to go on the stream with T1,the positive half cycle is not affected.So when ia>0,the trajectory remains the same,its shape is half arc,andφ∈(-∞,+∞);when ia=0,φ=0,and its shape is a straight line segment aswell.

The method of diagnosing IGBT open circuit fault through vector trajectory in the three-phase AC motor inverter is introduced into the IGBT fault diagnosis in the active power filter.

Fig.2 Current trajectory o f T1-T6 under the open-circuit fau lt

After acquiring the experiment data of the IGBT in APF open circuit fault and making vector transformation processing of it on the MATLAB platform,it is found that current vector trajectory in the APF have similar characteristicswith the current vector trajectory in the three-phase motor,IGBT open circuit faults in APF can be diagnosed by current vector trajectory.The current vector diagram with iαand iβbeing the horizontal axis and vertical axis respectively is drawn.As is shown in Fig.3,in the normal steady state,the graph of current vector is hexagon.And through the simulation results,it is shown that the six angles in the hexagon correspond to the six IGBT tubes(T1~T6)in APF.The corresponding relationship is shown in Fig.3.

Fig.3 Current trajectory o f APF under norm al operation

When IGBT open circuit fault occurs in APF,the vector trajectory of the electric current also has its characteristics.The current trajectories of T1~ T6when open circuit fault occur are shown in Fig.4 respectively.With failure in a phase as an example,when IGBT tube T1is disconnected,as the current vector trajectory being shown in Fig.4(a),in which the corresponding angle of T1ismissing on the basis of the normal hexagon.And when IGBT tube T2is disconnected,as the current vector trajectory being shown in Fig.4(b),in which the corresponding angle of T2ismissing on the basis of the normal hexagon.So are the situationswhen IGBT tubes T3~T6are disconnected.

Fig.4 Current trajectory o f T1-T6 under the open-circuit fau lt

According to the above analysis,it can be summarized thatwhen open-circuit fault occurs to various IGBT tubes of APF,the output of current vector trajectory graph share fixed characteristics.When the data of IGBT failure are got,intuitive judge can be made as to the location of the failure from the track diagram through the conduct of vector transformation,the process of which is convenient and intuitive.Two ideas are put forward by the diagnosis of IGBT fault location through APF output current vector trajectory by DSP.Idea 1[7],with the sampling of faultwaveform output providing the fault information,store themapping relationship between the fault location and fault waveform analysis results in the structure of the neural network through neural network learning.Then the system saves the learned neural network through DSP and the IGBT fault location in APF can bemade clear through DSP software on-line detection.

Idea 2,introduce physical quantity slope of half a cycleψ of current vector trajectory,and convert vector trajectory into the physical quantityψwhich DSP can directly identify

During normal operation,the current vector slopeψ is a changing physical quantity in a half cycle,and when the IGBT open circuit fault occurs,the current vector slopeψ is a constant in a half cycle.The relationship between IGBT fault location and half cycle bits of value is shown in Table 1.DSP calculates the collected current and gets half cycle of current slope.Then compare the phase current polarity ikwith the value of DSP in table 1,the location of IGBT tube fault can be identified and the six light-emitting diodes(LEDs)will show the corresponding fault position of IGBT.

Tab le 1 Fau lt location o f IGBT and the value o fψ

Thismethod does not need to detect the current polarity of phase current ik,instead,DSP only needs to compare the three constants to judge the fault bridge arm in IGBT,which simplifies the algorithm of detecting fault in IGBT through DSP software.The flow chart of themain program of detecting IGBT open-circuit fault through software is shown in Fig.5.

Fig.5 Flow chart o f the m ain p rogram of detecting IGBT open-circuit fault through DSP

3 Realize the fau lt-tolerant control of APF [8]

3.1 APF fault tolerant topology structure

APF fault tolerant topology structure is shown in Fig.6.On basis of the conventional three-phase sixswitch shunt APF,a phase bridge arm and three three-terminal two-way thyristor switches are added.In normal work,a,b,c three-phase accesses system work,three-terminal two-way thyristor switches TRa,TRb and TRc are disconnected,and D1and D2as backup bridge arms are not accessed into the system.APF in this situation is a conventional three-phase sixswitch shunt APF.When the open circuit fault of the APF system occurs,disconnect the fault phase,access the backup bridge arm into APF system under the control of the three-terminal two-way thyristor switches TRa,TRb and TRc to replace the fault phase.Comparing with the backup a complete APF topology,this topology structure reduces the cost under the circumstance of not switching algorithm andmaking the compensation effect the samewith the original system.Besides,when compare with the topology of the APF based on the three-phase four-switch,this topology structure can get better compensation effect without the necessity of switching control algorithm at the cost of a tiny increase of cost.It can be said that this kind of topological structure of redundant single bridge arm combines the advantages of the above two kinds of fault tolerant topology structures and is ideal in terms of both cost and compensation effect.

Fig.6 APF fau lt tolerant topo logical structure of redundant sing le bridge arm

3.2 Realize the fault-tolerant control of APF [9]

In the previous section,the APF fault tolerant topological structurewas introduced.When IGBT failure occurs,disconnect the fault phase and access to the backup bridge arm so as to make the system go on with stable operation in the fault.The key of the faulttolerant control of APF lies in how to disconnect the fault phase and how to access the backup bridge arm when fault happens.

The three-phase bridge arms a,b and c of APF are respectively connected to the normally closed contacts of the three relays.During normal operation,the switches of relays are closed and the three phase bridge arm access into the system.When a failure occurs,DSP drive pulse signal to transmit high level signals to the fault phase relay,control the fault phase relay to disconnect and thus disconnect the fault phase bridge arm.

APF backup bridge arm is disconnected during normal operation,and in the case of open circuit fault,accessed to the circuit to replace the fault phase.A bidirectional thyristor switch is chosen to control the on and off of the backup bridge arm in that a bidirectional thyristor switch is able to exert negative or positive grid signal to conduct.Once the bidirectional thyristor switch begins to conduct,the state of conduction can keep on even if the trigger voltage is disconnected.Only when the current of the first anode A1and the second anode A2is less than tomaintain current or when the voltage polarity of A1and A2changes,the bidirectional thyristor switch will be shut off,when only by triggering voltage again can the bidirectional thyristor switch be conducted.When fault occurs,the trigger latch pulse signal conveys a persistently high level signal to the bidirectional thyristor switch through DSP drive pulse signal until the bidirectional thyristor switch is conducted and the backup bridge arm is accessed.Since the overload ability of a bidirectional thyristor switch is bad,it is necessary to string a fast fuse into the bidirectional thyristor switch TRa,TRb and TRc.In this case,when errors in circuit overload or DSP software lead to awrong trigger,fusing the fast fuse quickly will protect the circuit and switch.The rated current value of the fast fuse should be set 1.5 times of the average current of the bidirectional thyristor.

4 Analysis of the sim u lation

In this article,open circuit fault detection,isolation and fault-tolerant control of IGBT in the APF system which have been shown in Fig.1 aremodeled and simulated on the MATLAB simulation platform.Simulation parameters contains:three-phase grid power source AC voltage with its source amplitude is380 V,50 Hz frequency,the DC side voltage is 800 V,the inverter DC side capacitor is6 000μF,the output filter inductance is 3mh,the load of themain circuit is three-phase rectifier circuit,and the load of the rectifier circuit is 25Ωin resistance and 1 mh in inductance.

This simulation experiment sets the open circuit fault of IGBTmanually,and verifies the quick detection of IGBT open circuit fault by software.After the failure,switch the fault bridge arm and redundant bridge arm and access the control signal into redundant bridge arm and then APF system still can keep stable operation in which the compensation effect is good.

Fig.7(a)is the grid current waveform and current THD(Total Harmonic Distortion)before APF compensation.It can be seen from the diagram that there aremultiple harmonics before compensation,THD is as high as 30.15%and the harmonic content is very high.Fig.7(b)shows the grid currentwaveform and current THD(Total Harmonic Distortion)after the APF compensation.It can be seen from the diagram that the current waveform is reaching sine wave after the compensation,THD reduces to 3.62%.That is,the harmonic content is greatly reduced and the compensation effect is good.Fig.7(c)is the APF DC side voltagewaveform.As can be seen from thewaveform that DC side voltage approximates linear position of 800 V after 0.1 second of oscillation,which corresponds to the DC voltage 800 V given in advance.That reveals that the DC side control algorithm is good in that it can make the DC side stability at a given value so as to ensure the stable operation of system.

Fig.7 The sim u lation resu lts o f before and after compensation

5 Conclusions

This paper brings up with an idea of locating IGBT open circuit fault in the APF based on software testing and further analysis is done on this idea.Meanwhile,fault-tolerant topological structure of redundant the single bridge arm is proposed for fault-tolerant control of APF and the method of switching fault phase and redundant bridge arm when IGBT failure occurs is provided.Finally,a simulation model is built in the MATLAB platform to carry on the simulation test on APF fault-tolerant system.And this simulation experiment proves the feasibility of the diagnosis of fault and fault tolerant topology structure proposed in this paper and their good compensation effect.

Acknow ledgem ents

This paper is supported by National Natural Science Foundation of China(No.61174107).

[1]Jia Yu,Luo An,Tang Jie.Series resonance of active power filter and its engineering application research[J].Electrical applications 2007,26(3):57-59.

[2]Wang Rui,Zhao Jin,Liu Yang.A comprehensive investigation of four-switch three-phase voltage source inverter based on double Fourier integral analysis[J].IEEE Trans on Power Electronics,2011,26(10):2774-2787.

[3]Li gang,F(xiàn)an Xiaoping,Peng Jinjie.Fault-tolerant active power filter based on 3-phase 4-switch structure[J].Proceedings of the CSU-EPSA),2013,25(30):88-92.

[4]Dong Weijie,Bai Xiaomin,Zhu Ninghui.Research on fault diagnosis and fault tolerant control of active power filters[J].Proceedings of the CSEE,2013,33(18):65-72.

[5]Trabelsi M,Boussak M,Gossa M.Multiple IGBTs open circuit faults diagnosis in voltage source inverter fed induction motor usingmodified slope method[C]//International Conference on Electrical Machines,Rome,2010:1-6.

[6]Chen Dong,Liu Zhenxing.Research on fault diagnosis of PWM rectifier[D].Wuhan:WUST,2012。

[7]Zhang Zuoliang,Tang Chaohui,Hu Zhikun.An Intelligent fault diagnosis system of inverter circuits[J].Computer Engineering& Science,2008,30(3):136-138.

[8]She Yan,Sun Yun lian.Based on DSP implementation of symmetric SVPWM vector control variable frequency speed regulation system[J].Electrical applications,2005,24(4):81-84.

[9]IVONNE Y B,Sun Dan,Liu Xue.Inverter fault tolerant reconfiguration control of permanentmagnet synchronousmotor drives[J].Power electronic technology,2008,42(7):36-36,82-83.

一種有源電力濾波器中IGBT故障診斷與容錯(cuò)控制研究

龔 誠(chéng)1,2*,劉振興1,2,李 翠1,2,馮 凱1,2

1.武漢科技大學(xué)信息科學(xué)與工程學(xué)院,武漢 430081
2.武漢科技大學(xué)冶金自動(dòng)化與檢測(cè)技術(shù)教育部工程研究中心,武漢 430081

針對(duì)APF(有源電力濾波器)逆變器中IGBT在長(zhǎng)期運(yùn)行時(shí)容易出現(xiàn)故障的情況,提出一種基于DSP軟件檢測(cè)定位IGBT故障的方法以及APF容錯(cuò)拓?fù)浣Y(jié)構(gòu)。分析了IGBT開(kāi)路故障診斷算法,提出了通過(guò)DSP軟件程序?qū)崿F(xiàn)故障診斷的方法,同時(shí)給出APF容錯(cuò)拓?fù)浣Y(jié)構(gòu)以及容錯(cuò)控制實(shí)施方法,在Matlab/Simulink仿真平臺(tái)建立相應(yīng)的APF控制系統(tǒng)仿真模型,通過(guò)仿真實(shí)驗(yàn)驗(yàn)證了該控制方案的可行性。

有源電力濾波器;IGBT;軟件檢測(cè)故障;容錯(cuò)控制

10.3969/j.issn.1001-3881.2015.06.019 Document code:A

TN713+ .8

09 October 2014;revised 30 October 2014;accepted 22 December 2014

猜你喜歡
故障診斷科技故障
故障一點(diǎn)通
科技助我來(lái)看云
科技在線
科技在線
奔馳R320車(chē)ABS、ESP故障燈異常點(diǎn)亮
科技在線
因果圖定性分析法及其在故障診斷中的應(yīng)用
故障一點(diǎn)通
江淮車(chē)故障3例
基于LCD和排列熵的滾動(dòng)軸承故障診斷
主站蜘蛛池模板: 国产剧情无码视频在线观看| 一区二区三区高清视频国产女人| 91视频日本| 中文字幕欧美日韩| 国产女人18水真多毛片18精品| 日韩天堂在线观看| 99在线视频免费| 久久久久青草大香线综合精品| 国产成人AV综合久久| 福利片91| 国产女人水多毛片18| 欧美色99| 亚洲第一视频免费在线| 国产不卡国语在线| 亚洲欧美国产五月天综合| 538国产在线| 中文字幕调教一区二区视频| 日本一区二区三区精品AⅤ| 丰满少妇αⅴ无码区| 国产精品一区二区在线播放| 国产精品入口麻豆| 午夜在线不卡| 99精品这里只有精品高清视频| 久久午夜夜伦鲁鲁片不卡| 日韩黄色大片免费看| 欧美成人免费午夜全| 国产成人喷潮在线观看| 日韩精品一区二区深田咏美| 亚洲色图狠狠干| 亚洲成人网在线播放| 亚洲精品卡2卡3卡4卡5卡区| 欧美一级视频免费| yy6080理论大片一级久久| 亚洲综合久久一本伊一区| 国产乱肥老妇精品视频| 国产精品lululu在线观看| 在线看片中文字幕| 亚洲国产精品日韩欧美一区| 久久精品无码专区免费| 在线观看免费人成视频色快速| 欧美一级高清免费a| 91精品国产自产91精品资源| 国产精品视频导航| 欧美亚洲中文精品三区| 成年A级毛片| 熟女视频91| 亚洲精品午夜天堂网页| 日韩毛片在线播放| 国产精品精品视频| av性天堂网| 影音先锋亚洲无码| 久久伊伊香蕉综合精品| 69视频国产| 18禁不卡免费网站| 伊人久久精品亚洲午夜| 国产精品大白天新婚身材| 91精品在线视频观看| av免费在线观看美女叉开腿| 欧美激情综合一区二区| 97在线碰| 成年片色大黄全免费网站久久| 国产黄色视频综合| 亚洲精品亚洲人成在线| 一级毛片在线免费看| 久久精品这里只有精99品| 国产亚卅精品无码| 精品国产欧美精品v| 亚洲国产综合精品一区| 国产黄在线免费观看| 色成人综合| 国产乱视频网站| 国产成人1024精品| 理论片一区| 日韩a级毛片| 亚洲一道AV无码午夜福利| 午夜视频在线观看区二区| 福利视频久久| 2021国产精品自产拍在线观看| 在线观看国产网址你懂的| 久久久久夜色精品波多野结衣| 九九免费观看全部免费视频| 国产尤物jk自慰制服喷水|