牛茂龍 張國軍 鄭軍偉
【摘 要】隨著核電廠自動化程度的提高,DCS在核電廠中的應用越來越廣泛,DCS中的電路板容易受外界強電或感應電影響而損壞。文章介紹了某核電廠調試期間電氣配電盤感應電引起DCS機籠模件燒毀的過程分析及感應電產生的原因。這種分析問題的方法和思路對解決DCS受干擾問題有一定指導和借鑒意義。
【關鍵詞】核電廠;電氣配電盤;感應電;DCS;IO模件
中圖分類號: TM623 文獻標識碼: A 文章編號: 2095-2457(2018)04-0129-002
The Root Cause Analysis of DCS Cage Mould in a Nuclear Power Plant
NIU Mao-long ZHANG Guo-jun ZHENG Jun-wei
(China guangdong nuclear engineering co.,LTD.,shenzhen guangdong 518000,China)
【Abstract】With the improvement of the automation degree of nuclear power plants,DCS has become more and more widely used in nuclear power plants,and the PCB in DCS can be damaged by external strong electricity or inductive power.This paper introduces the process analysis and the causes of the burning of DCS cage mold by electric distribution panel during the commissioning of a nuclear power plant. The method and idea of this kind of analysis are helpful to solve the interference problem of DCS.
【Key words】Nuclear power plant;Electric switchboard;Induction;DCS;IO module
0 引言
某核電廠是我國在翻版加改進的基礎上自主設計、建造的百萬千瓦級壓水堆核電廠,采用了德國西門子公司的非安全級Teleperm-XP和安全級Teleperm-XS全數字化DCS儀控系統。在調試過程中,發生了DCS控制柜機籠模件燒毀的事件。經調查分析,確認了電氣配電盤產生感應電是模件燒毀的根本原因。設備廠商對電氣配電盤現場改造后徹底消除了感應電的產生,排除了DCS系統安全運行的一個隱患。
1 事件概述
2010-11-18 15點37分某核電廠2號機主控室監視畫面突發煙霧探測報警,同時操縱員接到現場工作人員報警電話,報告4LX廠房房間4KCP561AR控制柜冒出煙霧且伴有火花。經現場檢查4KCP561AR機柜,發現6個機籠電源分配保險熔斷,CA層IO模件工作指示燈全部處于報警狀態,柜內CA層機籠模件有燒焦痕跡,電路板焊錫融化,如圖1。
隨后儀控專業牽頭、電氣和工藝系統專業配合的調查小組對事件原因進行調查分析。
2 原因查找
西門子Teleperm-XP(T2000)DCS系統包括控制柜、端子柜與電源柜等,每臺控制柜主要由CPU、IO模件及附屬元件組成,機籠背板是機柜總線的一部分,負責CPU與IO模件的通訊,并給IO模件分配工作電源。……