閆俊明 楊曉芳




摘要? 重點對煤層氣發電站中的抽采泵站防雷采用不同形式接閃器進行分析,并根據實際案例進行分析驗證,得出在瓦斯泵房面積較大的情況下,可優先考慮選擇4支等高接閃桿作為防雷保護,若與防雷要求不相符,可選擇2根接閃線。
關鍵詞 煤層氣發電站;瓦斯泵房;直擊雷防護
中圖分類號:TM863 文獻標識碼:A 文章編號:2095-3305(2019)01-074-02
DOI: 10.19383/j.cnki.nyzhyj.2019.01.028
Application of Direct Lightning Protection Tech?鄄nology in CBM Power Station
YAN Jun-ming? et al(Yangquan Meteorological Bureau, Yangquan, Shanxi 045000)
Abstract The lightning protection of drainage pumping station in the CBM power station was analyzed with different forms of lightning arrester, and the analysis and verification were carried out according to the actual case. It was concluded that under the condition of large area of the gas vacuum pump room, 4 lightning rods with equal height could be selected as the priority for lightning protection, and 2 lightning rods could be selected if it was inconsistent with the lightning protection requirements.
Key words? ?CBM power station; Gas vacuum pump room; Direct lightning protection
煤礦瓦斯抽放站是對瓦斯抽送和排放的場所,其內部瓦斯氣體體積較高且有很多瓦斯管道,屬易燃易爆場所,對煙火防護要求較高。通常情況下,瓦斯抽放站大都在高瓦斯礦井附近建造,與城區相距較大距離,位于荒野或山區,易遭受雷擊。雷擊產生火花和高溫很容易引爆瓦斯抽放站中易燃易爆物質,引發火災或爆炸,嚴重威脅人們生命財產安全。
1 避雷針防護范圍原理
滾球法主要是基于雷閃電氣幾何數學模型,設計原理是以雷擊距離作為半徑球體,沿著電力設備、建筑物等需要防直擊雷部位各方向進行滾動,一旦球體碰觸到接閃器,如作為接閃器的金屬體或直接接觸到接閃器及地面包括與大地直接接觸且能承受雷擊金屬物,卻不會碰觸到需要被保護的部位時,該部位就是在接閃器有效保護范圍內。
2 各種類型接閃器防雷保護范圍
煤礦瓦斯泵房建設高度大都在8~15 m,根據《煤礦安全規程》(2016年)中相關要求抽采瓦斯泵站放空管高度應距離泵房房頂3 m以上,放散管管口高度應在11~18 m,即放散管管口高度11 m左右,在選用單、雙支接閃桿或單根接閃線作為接閃器使用時,借助滾球法確定的保護范圍仍不能覆蓋放散管保護區域。……