Power cost minimization in data centers Via Lyapunov optimization①

2016-12-29 05:34:27ZhangRanWanJianxiong
High Technology Letters 2016年4期
關鍵詞:思想

Zhang Ran (張 然), Wan Jianxiong

(*School of Mathematics and Statistics of Central South University, Changsha 410083, P.R.China)(**School of Information Engineering, Inner Mongolia University of Technology, Hohhot 010051, P.R.China)

?

Power cost minimization in data centers Via Lyapunov optimization①

Zhang Ran (張 然)②*, Wan Jianxiong**

(*School of Mathematics and Statistics of Central South University, Changsha 410083, P.R.China)(**School of Information Engineering, Inner Mongolia University of Technology, Hohhot 010051, P.R.China)

With the advent of big data, the demand for computing has been increasing in a very large scale for the past decade, so geographically distributed data centers are erected in the direction of cloud computing development. A Lyapunov optimization approach is considered for the problem of minimizing energy cost for distributed Internet data centers (IDCs). By capturing the power cost of servers and cooling systems, the Lyapunov optimization technique is formulated to design a decisive strategy that offers provable power cost minimization and QoS guarantees. The algorithm performance and effectiveness are validated via simulations driven by real world traces.

power cost, quality-of-service (QoS), workload

0 Introduction

The increasing Internet services and cloud computing have stepped into people lives in recent years so that big data and computation are migrated to or hosted on the Internet data centers (IDCs). The total construction area of a huge IDC is 300,000 square meters, which can host more than one million high-performance servers. However, consumed energy in IDCs and its cost have been gradually out of control. Qureshi et al. discovered that many IDC operators consumed more than 10 million dollars on their annual electricity bills[1], so the research focuses on how to reduce energy consumption and electricity cost of IDCs.

Most previous jobs on power management paid close attention to how to reduce the total energy consumption. However, apart from the energy consumption, electricity price should be more concerned too since the electricity prices in western countries exhibit time and location diversities[2-5]. Although the above researches probed the energy cost spent in electricity from servers and practical applications, they ignored another aspect of energy cost, cooling system. Zhang designed and evaluated TEStore exploiting thermal and energy storage techniques to cut the electricity bill for data center cooling without causing servers in a data center to overheat[6]. Nevertheless, the study simply reduced the total cost in a coarse-grain pattern. Their research ignored the widen difference of server-temperatures across diverse server rackets and applications.

An expense minimization of IDC’s electricity power (EMIEP) problem is formulated in this paper to minimize time-averaged expected energy cost subject to QoS and average temperature constraints. Meanwhile, the research designs an algorithm leveraging the Lyapunov Optimization technique to approximately solve the EMIEP problem and use real workload trace from Ordos UniCloud Technology Co., Ltd. to simulate the above algorithm. Numerical results illustrate that the presented algorithm can reduce total energy cost as well as guarantee QoS and temperature constraints.

1 System model

This section discovers a system model shown in Fig.1 and formulates the EMIEP problem. IDC physically consists of rackets of servers and is logically made up of a number of applications, each of which schedules its servers to process the arriving service. All requests preparing to enter an application share the same workload queue and follow the rule that the requests in buffer will be scheduled to the currently idle server. Quality-of-service (QoS) requirement must be considered in each application.

The running servers generate massive waste heat inevitably. For the sake of the reliability of the servers, a computer room air conditioner (CRAC) is used to regulate the server temperatures by sucking cold air into the server racks, pushing waste heat out of the machine room, and recycling the inside air via the air chilling unit. Fig.1 exhibits the air flow of the system. The light arrow represents cold air and the brunet one symbolizes hot air exhausted from the racks. Apart from the above CRAC, an indoor air conditioner maintains the machine room temperature to predetermined Tsp.

Fig.1 Layout of IDC Applications

The whole industry is confronted with huge cost of energy consumption, including server energy consumption and cooling energy consumption. This paper formulates the problem of minimizing the total energy cost of the data center subject to QoS and server temperature constraint. The formulated model can be simply described as follows:

minserver power cost + cooling power cost

subject to:

QoS constraint, for each application

Average temperature constraint, for each server

This problem describes three control variables: number of servers for each application, cold air temperature and electricity price discussed in details in the following sections.

2 Problem formulation

2.1 Energy cost model

2.1.1 The server side

Let J be the total number of applications hosted in IDC. At time slot t, define p(t), ej(t), Lj(t), and mj(t) as the electricity price, energy consumption for a single server, the workload, and the number of servers for application j∈[1,…,J], respectively. Refs[7,8] presented a linear function to display the relationship between power consumption and the server load as follows:

(1)

where a1is the marginal energy consumption for CPU and a2denotes the server energy consumption except CPU. The total energy consumption of an application j is Ej(t)=mj(t)×ej(t)=a1Lj(t)+a2mj(t), and the total server energy cost in IDC is

(2)

2.1.2 The air chiller side

C(t)=cfρ(Tsp-Tc(t))

(3)

The energy cost is

PC(t)=p(t)×cfρ(Tsp-Tc(t))

(4)

Obviously, it is the sum of PS(t) and PS(t) that equals the total power cost of the data center.

2.2 Constraints

2.2.1 QoS constraint

(5)

2.2.2 Temperature constraint

At steady state, the temperature of server j can be controlled by the inlet cold air temperature Tc(t) and the CPU energy consumption ej(t):

(6)

where ζ is the heat exchange rate expressed in K·s/J. The processor and motherboard reliability of a server is mainly influenced by temperature gradient and thermal stress in a production data center. With respect to reliability issue, the expected server temperature must be maintained below a certain threshold Tmax. Plugging Eq.(1) into Eq.(6) yields:

(7)

2.3 Problem formulation

After some alternations of Eq.(5) and inequation(7), now define the EMIEP problem as follows:

(8)

subject to:

(9)

≤0,?j, t (10)

Tmin≤Tc≤Tmax

The EMIEP problem cannot be easily solved due to the following reasons: 1) The unknown probability distribution of Lj(t) and p(t) makes the expectation in Eq.(8) and constraint (10) computationally troublesome; 2) Traditional methods to deal with dynamic optimization problems such as dynamic programming suffers from the curse of dimensionality, i.e., the computation complexity grows exponentially with problem size. Therefore, a modern method will alternate the old approach to approximately solve this problem.

3 A Lyapunov approach to solve EMIEP problem

This section first relaxes constraint (10) and uses the Lyapunov optimization theory to obtain an optimal solution.

3.1 Relaxing the EMIEP problem

Constraint (10) can be relaxed into

≤0,?j (11)

The relaxation suggests that the expected server temperature is occasionally beyond the temperature bound without destroying reliability as long as the time-averaged expected temperature is within the acceptable range.

Replacing constraint (10) in the original problem by constraint (11) leads to an relaxed version of EMIEP. Constraint (11) can be further transformed into:

+a2mj(t))-Tmaxmj(t)}≤0

由于隴西縣的絕大部分勞動力受長期自然經濟的影響,小農意識濃厚,思想保守,滿足于現狀和眼前利益,缺乏發展致富的成就動機,加之大多數貧困勞動力持有小富即安的陳舊思想,致富意識淡薄,缺乏脫貧致富的內生動力,存在“等靠要”思想。

(12)

To satisfy constraint (12), EMIEP can be transformed into a queue stability problem. Define virtual queue Zj(t) with update Eq.(13).

Zj(t+1)=max{Zj(t)+mj(t)Tc(t)+ζ(a1Lj(t) +a2mj(t))-Tmaxmj(t),0}

(13)

3.2 The objective function

The Lyapunov optimization framework subtly designs a control algorithm that chooses actions for all t to yield a time average expectation of the objective function value close to optimal solution with the mean-stable virtual queue Zj(t). The algorithm changes the original problem into an alternative, minimizing the time average of a cost function subject to queue stability.

Let Zj(t) be a concatenated vector of all virtual queues with update Eq.(13). Define the Lyapunov function:

(14)

Define Δ(Ζ(t)) as the conditional Lyapunov drift for slot t:

(15)

where the expectation depends on the control policy and random workload arrivals.

Instead of taking control actions to directly minimize Eq.(8), the Lyapunov optimization seeks to minimize a bound of the following drift-plus-penalty function

Δ(Ζ(t))+VE{p(t)(E(t)+C(t))|Z(t))}

(16)

where V≥0 symbolizes an “importance weight” on how much the algorithm emphasizes cost minimization. In section 6, an algorithm minimizing Eq.(16) will achieve a close-to-optimal solution while stabilizing Ζ(t).

The drift-plus-penalty objective function Eq.(16) can be bounded by the following

Δ(Ζ(t))+VE{p(t)(E(t)+C(t))|Ζ(t))}

+ζ(a1Lj(t)+a2mj(t))-Tmaxmj(t))|Ζ(t))}

+VE{p(t)(E(t)+C(t))|Ζ(t))}

(17)

where B is a constant defined as B=mmaxTmax+ζ(a1Lmax+a2mmax). The designed algorithm minimizes the right-hand-side of Eq.(17).

3.3 Algorithm design

The objective function of problem Eq.(8) can be rewritten as

+cfρ(TSP-Tc)]

(18)

The existing cross term of control variables plagues the solution of the problem. However, fixing Lj(t) and p(t) can simplify the solution for mj(t) by creating a linear function. To see that, dropping the constant terms in Eq.(18) yields

+Vp(t)a2mj(t)}-Vp(t)cfρTc

(19)

Rearranging (19) yields

-Vp(t)cfρTc

(20)

Algorithm1 EMIEP:Choosingthebestmbestj(t)fortheDrift?Plus?PenaltyAlgorithm1:Determinetheupperboundofmj(t)asmmaxj2:Calculatetheminimumofmj(t):mminj(t)=1Dj+Lj(t)μ3:Studythecoefficientofmj(t):4:ifZj(t)(Tc+ζa2-Tmax)+Vp(t)a2>0then5: returnmminj(t)6:else7: returnmmaxj8:endif

The next step is to test all possible cooling air temperatures to find optimal Tc. This can be done via Algorithm 2.

Algorithm2 EMIEP:MinimizingtheDrift?Plus?PenaltyAlgorithm1:Define: interval:Setofdecisionepoch Temperature:Setofpossiblecoolingairtemperature. Applications:Setofapplications. Fobj:Thevalueofobjectfunction DPP[Tc]:ThevalueofLyapunovDrift?plus?PenaltyatTc2:forallt∈intervaldo3: forallTc∈temperaturedo4: CallAlg.1,acquirembestj(Tc)forallj5: Fobj←∑Jj=1p(Tc)(a1Lj(Tc)+a2mbestj(Tc))+p(Tc)?c?f?ρ(TSP-Tc)6: DPP[Tc]←∑Jj=1Zj(Tc){mbestj(Tc)Tc+σ(a1Lj(Tc)+a2mbestj(Tc))-Tmaxmbestj(Tc)}+V×Fobj7:endfor8:minTc←argminTcDPP[Tc]9:mbest(t)←m[minTc]10:minFobj(t)←Fobj[minTc]11:minServerprice(t)←serverprice[minTc]12:minCoolingprice(t)←coolingprice[minTc]13:Zj(t+1)←max{Zj(t)+mbest(t)?Tc(t)+ζ(a1?Lj(t)+a2?mbest(t))-Tmax?mbest(t),0}14:endfor

4 Performance analysis

This section first shows that the minimum time-averaged IDC energy cost can be achieved using a randomized stationary control policy independent of the virtual queue state Ζ(t). Then, a performance bound for objective function is derived.

Define E{p(t)(Eπ(t)+Cπ(t))} as the expected energy cost in the interval [1,…,T] under control policy π, and e*as the minimum achievable E{p(t) (Eπ(t)+Cπ(t))} over all possible π. If problem Eq.(8) is feasible, then for any δ>0, there is a policy π*which depends only on workload and power price which satisfies

E{p(t)(Eπ*(t)+Cπ*(t))}≤e*+δ

This result is a direct application of Theorem 4.5 in Ref.[9], which discovers that there is aqueue-independent randomized stationary yielding an energy cost arbitrary close to the optimum as long as the problem is feasible. Next the performance bound is given.

Theorem 1 Suppose that E{L(Ζ(0))}<∞. The following results yield:

1) The achievable total energy cost of the EMIEP algorithm can be bounded by

(21)

2) The virtual queue Ζ(t) is mean rate stable, i.e.,

(22)

According to the above theorems, the article concludes the [O(1/V), O(V)] tradeoff, i.e., the energy cost can be pushed arbitrarily closed to the optimum as V→∞.

5 Numerical evaluations

This section conducts extensive simulations to evaluate the proposed EMIEP algorithm.

5.1 System configuration

All data used in research were accumulated from four applications of Ordos Uni-Cloud Co., Ltd., after the authors had spent a week on their Internet Data Center (IDC). Because electricity in EMIEP relates to two factors: server power expenditure and cooling system, workload trace involved in server power contains mean request arrival rate shown in Fig.2 for interactive web service at intervals per hour.

To analyze energy cost consumed in applications, machine room Tspis set to 25℃. In the light of Ref.[9], the algorithm acquires the heat capacity and the density of the air as c = 1005J/kg.K and ρ =1. 205kg/m3at 25℃. Without loss of generality, the service rate of single server μ is normalized as 1 across all applications. If the minimal and maximal power consumption of a single server is 40W and 80W, parameters in Eq.(1) can be set to a1=40 and a2=40. Suppose that heat exchange rate is ζ=0.625K·s/J, the air flow rate is f =5m3/s, and the maximum allowable server temperature is Tmax= 60℃.

Fig.2 Workload trace involved in server power

5.2 Result analysis

Based on the above set parameters, the performance of the EMIEP algorithm is investigated and compared with a greedy policy, which is obtained by solving the following problem:

minPS(t)+PC(t)

(23)

subject to:

Note that problem (23) greedily minimizes power cost in current slot rather than the long term average power cost.

5.2.1 Total energy cost and delay

Fig.3 shows that dynamic programming price (DPP) is also a random variable. At the initial state, its number of samples is not enough that the expectation of objective function is over-estimated, but as time goes by, more samples will be obtained, which leads to more accurate estimation.

Fig.3 Value of drift-plus-penalty objective function with V=10

Different vertical ordinates shown in Fig.4(a), 4(b) and 4(c) individually denote total, server and cooling energy costs V, the horizontal ordinate, controls the weight of Lyapunov drift and objective function. The experiment also plots the performance of greedy strategy in the figure, as shown in Fig.4(a) and 4(b), the total and server energy costs descend in steps with the increase of V. In this way, the objective function is efficiently optimized. Though the cooling energy cost mildly increases at V=108, V=109and V=1010shown in Fig.4(c), this situation has not affected the general tendency of energy cost as V grows. When V grows to V=1011, this EMIEP outperforms greedy strategy.

(a) Total energy cost vs. V

(b) Server energy cost vs. V

(c) Cooling energy cost vs. V

The QoS (delay) for each application in Fig.7 discovers that the 10ms QoS requirement is met in this EMIEP strategy. Fig.5 and Fig.6 show the number of servers allocated to each application with time and the variation of drift-plus-penalty objective function, respectively. It can be shown that this EMIEP can effectively minimize the system power cost while ensuring QoS requirement.

Fig.5 Servers allocated to each application with V=10

Fig.6 QoS (delay)

5.2.2 Cooling temperature and server temperature

Compared with Fig.4(c), the variation trend of cooling cost in Fig.7 goes to different way. The case explains the fact that the lower the temperature of cooling air is set, the higher the cooling power consumption and cost.

Fig.7 Cooling air temperature vs. V

Since energy consumption directly influences server temperature, the server temperatures as shown in Fig.8 from four applications constantly keep heading up but occasionally fluctuate at V=109and V=1010in application 3 and 4. Raising V to 1011slightly increasing the average temperature, significant power cost savings can be obtained.

Fig.8 Server temperature vs. V

6 Conclusion

This work concentrates on greening the data center by minimizing time-averaged expected energy cost subject to QoS and average temperature constraints.

Since the workload distribution cannot be obtained in advance, it is challenging to design a dynamic control algorithm to achieve this goal.

To address this opinion, the algorithm leverage the Lyapunov Optimization technique and develop an algorithm to approximately solve the Expense Minimization of IDC’s Electricity Power problem. By evaluating the simulation experiment, the algorithm can be pushed arbitrarily close to optimal solution as control parameter V is raised. Based on real workload trace from Ordos Uni-Cloud Technology Co., Ltd.to simulate the proposed algorithm, numerical results illustrate that the algorithm can practically reduce total energy cost while guaranteeing QoS and temperature constraints.

[1] Qureshi A, Weber R, Balakrishnan H, et al. Cutting the electric bill for internet-scale systems. ACM SIGCOMM Computer Communication Review, 2009, 1:123-134

[2] Dou H, Qi Y, Wang P J, et al. Hybrid power control and electricity cost management for distributed internet data centers in cloud computing. In: Proceedings of the 10th International Conference on Web Information System and Application, Yangzhou, China, 2013. 394-399

[3] Yao J G, Liu X, He W B, et al. Dynamic control of electricity cost with power demand smoothing and peak shaving for distributed internet data centers. In: Proceedings of the 2012 IEEE 32nd International Conference on Distributed Computing Systems, Macau, China, 2012, 67: 416-424

[4] Wang C, Urgaonkar B, Wang Q, et al. A hierarchical demand response framework for data center power cost optimization under real-world electricity pricing. In: Proceedings of the 2014 IEEE 22nd International Symposium on Modeling, Analysis and Simulation of Computer and Telecommunication Systems, Paris, France, 2014, 45: 305-314

[5] Xin Z, Reda S. Power budgeting techniques for data centers.IEEE Transactions on Computers, 2015, 64(8):2267-2278

[6] Zhang Y W, Wang Y, Wang X. TEStore: exploiting thermal and energy storage to cut the electricity bill for datacenter cooling. In: Proceedings of the 8th International Conference on Network and Service Management International Federation for Information Processing, Las Vegas, USA, 2012, 1:19-27

[7] Kaushik R T, Nahrstedt K. A data-centric cooling energy costs reduction approach for big data analytics cloud. In: Proceedings of the 2012 International Conference on High Performance Computing, Networking, Storage and Analysis, Madrid, Spain, 2012, 1: 1-11

[8] Li S, Le H, Pham N, et al. Joint optimization of computing and cooling energy: analytic model and a machine room case study. In: Proceedings of the International Conference on Distributed Computing Systems, Macau, China, 2012, 1: 396-405

[9] Neely M J. Stochastic network optimization with application to communication and queueing systems.Morgan & Claypool,2010, 4:53-62

Zhang Ran, is a graduate pursuing Ph.D in School of Mathematics and Statistics of Central South University. He received B.S. in applied mathematics from Branch Campus of Peking University in 1994 and M.S in computer science from Xidian University in 2007. His research interests focus on probability and applied statistics, machine learning, IDC resource management, and data mining.

10.3772/j.issn.1006-6748.2016.04.003

① Supported by the National Natural Science Foundation of China (No. 61502255), the Inner Mongolia Provincial Natural Science Foundation (No. 2014BS0607), and the Science Research Project for Inner Mongolia College (No. NJZY14064).

② To whom correspondence should be addressed. E-mail: seran_zhang@126.com Received on Oct. 9, 2015

猜你喜歡
思想
轉化思想的應用
思想之光照耀奮進之路
華人時刊(2022年7期)2022-06-05 07:33:26
聚焦補集思想的應用
思想與“劍”
當代陜西(2021年13期)2021-08-06 09:24:34
艱苦奮斗、勤儉節約的思想永遠不能丟
人大建設(2019年4期)2019-07-13 05:43:08
“思想是什么”
當代陜西(2019年12期)2019-07-12 09:11:50
遞推思想及其應用
中等數學(2018年3期)2018-08-01 06:42:02
學思想 悟思想 用思想
中國鹽業(2018年21期)2018-03-05 08:06:10
把握轉化三要素 有效滲透轉化思想
聚焦補集思想的應用
主站蜘蛛池模板: 欧美在线观看不卡| 久草热视频在线| 激情影院内射美女| 噜噜噜久久| 四虎永久在线视频| 亚洲无码A视频在线| 伊人AV天堂| 国产无遮挡裸体免费视频| 中国国产高清免费AV片| 国产麻豆aⅴ精品无码| 亚洲天堂日韩av电影| 亚洲国产精品日韩av专区| 亚洲 欧美 偷自乱 图片| 在线无码av一区二区三区| 在线观看视频一区二区| 国产精品一区二区无码免费看片| 国禁国产you女视频网站| 国产理论最新国产精品视频| 色综合手机在线| 99在线视频精品| 天天色天天综合| 黄色a一级视频| 呦系列视频一区二区三区| 一本色道久久88| 91免费观看视频| 亚洲天堂免费在线视频| 国产精品自在在线午夜| 好紧太爽了视频免费无码| 日韩视频免费| 国产毛片久久国产| 久久网欧美| 久久综合丝袜长腿丝袜| 手机在线国产精品| 欧美日韩一区二区在线免费观看| 5388国产亚洲欧美在线观看| 国产精品无码制服丝袜| 午夜国产精品视频| 国产一区二区三区视频| 欧美成人一级| 亚洲欧美日韩中文字幕在线一区| 国产91成人| 久久久久88色偷偷| 日本精品视频| 国产日韩欧美在线播放| 99久久国产综合精品2023 | 亚洲国产欧美自拍| 亚洲国产成人精品无码区性色| 欧美成人精品一区二区| 欧美激情网址| 亚洲视频影院| 亚洲第一av网站| 国产sm重味一区二区三区| 热这里只有精品国产热门精品| 波多野结衣无码视频在线观看| 欧美日韩中文字幕在线| 毛片网站免费在线观看| 国产精品无码AⅤ在线观看播放| 在线国产综合一区二区三区| 91视频99| 日本一区高清| av在线5g无码天天| 久久国产亚洲偷自| 久久久噜噜噜| 九九九精品成人免费视频7| 国产在线观看第二页| 国产丝袜啪啪| 日韩a级毛片| 亚洲日韩久久综合中文字幕| 精品乱码久久久久久久| 97se亚洲综合在线天天| 性欧美在线| 亚洲最新地址| 五月六月伊人狠狠丁香网| 91网站国产| 香蕉eeww99国产精选播放| 日韩二区三区| 久久semm亚洲国产| 91小视频在线观看免费版高清| 国产草草影院18成年视频| 青青草原国产精品啪啪视频| 国产99免费视频| 国产高清精品在线91|