王小鵬 鞠海華



摘 要:消防水泵相比普通離心泵而言,有一些特殊要求,為使工程設(shè)計(jì)人員能盡快掌握消防水泵的特點(diǎn),根據(jù)實(shí)際工作經(jīng)驗(yàn),結(jié)合GB6245、NFPA20標(biāo)準(zhǔn)的要求,以及FM/UL認(rèn)證的要求,總結(jié)了煉化裝置中消防水泵選型時(shí)的注意事項(xiàng),供工程設(shè)計(jì)人員參考使用。
關(guān) 鍵 詞:消防水泵;注意事項(xiàng);GB6245;NFPA20;FM/UL認(rèn)證
中圖分類號(hào):TE 624 文獻(xiàn)標(biāo)識(shí)碼: A 文章編號(hào): 1671-0460(2015)07-1667-04
Analysis on Matters Needing Attention in Selection of Fire-Fighting Pumps for Refinery and Chemical Plants
WANG Xiao-peng1,JU Hai-Hua2
(1. China Huanqiu Contracting & Engineering Corporation, Beijing 100012, China;
2. Beijing Modern Vocational and Technical College, Beijing 101309, China)
Abstract: Fire fighting pump has special characteristics comparing with ordinary centrifugal pumps. In order to make the engineering designer know the characteristics, matters needing attention in selection of fire-fighting pumps for refinery and chemical plants were analyzed based on engineering experiences and the requirements of standard of GB6245, NFPA20, FM/UL certification.
Key words: Fire fighting pump; Matters needing attention; GB6245; NFPA20; FM/UL certified
煉化裝置的物料一般為易燃易爆介質(zhì),一旦發(fā)生火災(zāi),其危害性巨大。消防水泵是整個(gè)消防系統(tǒng)的“心臟”設(shè)備,因此消防水泵的選型就顯得非常重要。作為一名工程設(shè)計(jì)人員,必須清楚相關(guān)標(biāo)準(zhǔn)規(guī)范對(duì)消防水泵的技術(shù)要求,筆者根據(jù)多年的工作經(jīng)驗(yàn),將工程設(shè)計(jì)階段消防水泵選型的注意事項(xiàng)總結(jié)如下,供廣大工程設(shè)計(jì)人員借鑒。
1煉化裝置消防水泵的配置及適用標(biāo)準(zhǔn)
1.1 消防水泵的配置
根據(jù)消防水的來源不同,靠近海邊的裝置可能會(huì)采用海水消防泵,但大多數(shù)煉化裝置中都是使用淡水消防泵。從驅(qū)動(dòng)設(shè)備上看,一般是以柴油機(jī)驅(qū)動(dòng)和電機(jī)驅(qū)動(dòng),理論上也可選用蒸汽透平等其他驅(qū)動(dòng)機(jī),但消防泵要求快速啟動(dòng),蒸汽透平等其他驅(qū)動(dòng)機(jī)往往不能滿足要求,筆者執(zhí)行過的項(xiàng)目中均為柴油機(jī)驅(qū)動(dòng)和電機(jī)驅(qū)動(dòng)。煉化裝置中最為常見的配置是柴油消防泵+電動(dòng)消防泵+電動(dòng)保壓泵,每種類型的臺(tái)數(shù)的設(shè)置原則是在滿足水量要求的前提下盡量減少臺(tái)數(shù),以減少泵房占地面積,同時(shí)要考慮適當(dāng)?shù)脑O(shè)置備用泵的數(shù)量。……