主動式冷梁熱工性能仿真模型及實驗驗證

2015-04-29 00:00:00王昊斌田喆袁德奎段寶東
土木建筑與環境工程 2015年6期

摘要:以無限空間射流理論和表冷器換熱理論為基礎,對主動式冷梁的工作原理進行了分析。在假設條件下,建立了誘導送風模型和干工況表冷器換熱模型。結合這兩種模型,最終建立了主動式冷梁工作模型。在設定的5種靜壓箱靜壓值下,對主動式冷梁樣品的一次風量、二次風量、水側換熱量等熱工參數進行測試。選取誘導比和制冷量兩個表征冷梁性能的參數作為標準,對模型理論值與樣品實際值進行了一致性與差異性分析,驗證了所構建的主動式冷梁模型。

關鍵詞:主動式冷梁;熱工性能;仿真模型;實驗驗證

中圖分類號:TB 657.2 文獻標志碼:A 文章編號:1674-4764(2015)06-0128-06

Abstract:The working principle of active chilled beams (ACBs) was analyzed on the basis of unlimited space jet theory and cooler heat exchanger theory. Inducement ventilation model and cooler heat exchanger model were built under the assumptions. The two models were combined to establish ACBs model. Primary air volume, secondary air volume, water side heat transfer amount etc were measured in five specified static pressure value. Induction ratio and refrigerating capacity were selected as two standards of ACBs performance parameters. The results of the consistency and differences of theoretical value with practical value verified the established model.

Key words:active chilled beams;thermal performance;simulation model;experimental verification

輻射供冷空調技術于20世紀80年代興起于歐洲,在中國起步較晚[1]。許多研究表明,輻射空調系統比變風量空調系統更為節能[2-4]。在目前可持續發展的戰略背景下,輻射供冷系統成為一個綠色低能耗建筑首先考慮的空調系統,具有良好的發展前景[5]。主動式冷梁技術作為輻射供冷的空調末端技術,在中國發展迅速。由一些案例中得知,主動式冷梁系統仍有節能潛力尚未挖掘[6-8]。近年來,人們對冷梁的誘導器結構和運行系統做了大量的研究和改進[9-12],但目前在對冷梁的研究中尚無針對主動式冷梁建立仿真模型。本文在簡化假設的前提下,對主動式冷梁誘導送風規律和傳熱規律進行了分析,為主動式冷梁建立了仿真工作模型。對主動式冷梁樣品風側誘導性能和換熱器換熱性能進行了實驗研究,將實驗結果與理論計算進行對比,并對二者的差異性和一致性進行了分析。

1 主動式冷梁熱工性能模型建立

主動式冷梁工作原理如圖1所示。以供冷工況為例,經熱濕處理后的一次風送入誘導器,在誘導作用下產生二次風(室內熱空氣),二次風在換熱器處換熱后溫度降低,和一次風混合后送入室內,達到降低室內溫度的目的[13-14]。基于此,將主動式冷梁分為一次風誘導過程和二次風的換熱過程兩部分分別研究。

1.1 一次風誘導過程模型

一次風送入主動式冷梁靜壓箱后,經噴嘴高速噴出,通過誘導作用卷吸室內二次風通過換熱器發生換熱作用,該誘導作用發生在冷梁的誘導器處,靜壓箱則起到均壓的作用。如圖2所示,冷梁噴嘴直徑為d,噴嘴中心距側板的距離為l1,噴嘴中心距擋板的距離為l2。

以單個噴嘴誘導送風為研究對象,過噴嘴中心軸線且垂直于圖面的平面將射流流場分為兩部分,分別記為部分Ⅰ和部分Ⅱ,射流流場與側板和擋板搭接時的射程分別為s1和s2,噴嘴出口處的風量為Q1,部分Ⅰ和部分Ⅱ的風量分別記為QⅠ和QⅡ。由無限空間圓斷面淹沒射流理論,分別計算部分Ⅰ和部分Ⅱ的流場風量。

考慮到主動式冷梁誘導腔的誘導作用是非常復雜的,在對此處誘導送風理論進行研究過程中進行適當的簡化,同時,保證可靠性和準確度。假設條件如下:

1)忽略側板及擋板對射流流場的影響,將受限空間射流理想化為自由射流,射流流場斷面為圓形。

2)當射流與擋板和側板剛剛搭接后,或相鄰噴嘴射流流場邊界層剛好搭接后,就不再產生誘導效果。

3)忽略相鄰射流對流場的影響,即相鄰射流互不混合,搭接后緊密流動。

4)忽略表冷器側的阻力對二次風量的影響。

5)假設射流不射入換熱器上方區域,即射流完全射入冷梁擋板和側板所圍城的夾縫區域。

誘導送風過程中誘導能力的大小關系到二次風量Q2的大小,誘導能力越強,卷吸的二次風量越多,相同條件下產生的換熱量越大。本文引入誘導比的概念來衡量誘導能力的大小,定義主動式冷梁的誘導比為二次風量與一次風量的比值

1.2 表冷器干工況傳熱模型

主動式冷梁表冷器供冷工況的供水溫度應高于室內回風溫度對應的露點溫度,以防止結露的發生,即表冷器處于干工況運行模式,整個供冷過程不產生冷凝水。主動式冷梁目前多采用管翅式表冷器作為換熱元件,銅管鋁片結構能夠使換熱器達到較高的換熱效率,室內二次風由于一次風的誘導作用,經過管翅式換熱器后溫度逐漸降低,與一次風混合后送入室內。

1.3 主動式冷梁工作模型

將誘導送風模型與表冷器干工況換熱模型相結合,即得到主動式冷梁換熱模型。連接誘導送風模型與表冷器干工況換熱模型的紐帶為二次風。由對誘導送風模型和表冷器干工況換熱模型的分析可知,當主動式冷梁結構參數一定時、主動式冷梁輸入的一次風量一定時,可通過式(1)和式(4)計算得到主動式冷梁誘導的二次風量;通過二次風量可以計算得到主動式冷梁表冷器翅片表面對流換熱系數,已知供水參數和表冷器詳細結構參數的情況下,可以通過式(9)計算得到主動式冷梁水側理論換熱量。由此可得到主動式冷梁水側換熱量與一次風量的關系式。

由表2得知,測試冷梁的誘導比實測值與理論值相差不多,模型計算值與實驗測試值符合性良好,則可將其作為主動式冷梁工作模型的驗證,對結果進行相應的分析。由于實驗過程中未對經過表冷器后的空氣溫度進行測試,根據熱力學第一定律,本文通過水側換熱量計算得到經過表冷器后的空氣溫度,進而求得二次風進出換熱器平均溫度tf2。根據供水溫度及流量可求得冷水與銅管換熱的對流表面傳熱系數,根據換熱器結構參數可求得銅管及鋁片的熱阻。在計算肋片側熱阻的過程中,將表冷器等效為環肋模型,即將翅片等面積分到每根銅管上,建立圓管環肋換熱模型進行計算。將求得的參數和一次風量及理論誘導比等參數帶入式(10),即可求得主動式冷梁工作時的理論換熱量。

實驗分別測試了冷梁在4種噴嘴間距時的換熱量,在不同靜壓箱靜壓和換熱溫差實驗條件下,共進行了300組實驗,選取其中靜壓箱靜壓值為40 Pa與80 Pa的數據進行分析。圖4為測試冷梁噴嘴間距不同時,在不同換熱溫差下的理論制冷量與實際制冷量對比圖。

由圖4可以看出實際與理論制冷量曲線在不同噴口間距情況下走勢出入不大,證明了建立的仿真模型在實際應用中具有一定的準確性。但理論值與實際值之間的誤差則需要做進一步的誤差分析。

使用完全的實驗數據與模型計算結果進行比對,模型計算值與實驗值的相對誤差保持在15%以內,各實驗工況下計算值與實驗值誤差分布規律如圖5所示。由圖5可知,模型計算值與實驗值的最大相對誤差在-10%~10%范圍內的點占總數據點的比例為77%,說明模型計算值與實驗測試值差異性不大。

采用Bland-Altman方法對各工況實驗值和模型計算值進行一致性分析,如圖6所示。Bland-Altman方法是一種比較常用的用于分析模擬數據和實驗數據一致性的方法,它可以把兩種不同方式得到的數據的定性和定量分析結合到一起,用圖表的形式形象的反映出來。Bland-Altman方法不僅包含了數據得到的過程的隨機誤差,同時也將系統誤差納入到了考慮的范圍內,能夠比較全面準確地反映不同方法得到的數據的一致性。限于篇幅,文中未列出各工況具體的實驗條件及實驗結果。

由圖6可以明顯地看出兩種數據的一致性較好,大部分數值點落在在95%置信區間范圍內。經計算,超出95%的置信區間的數值點占總數值點的比例為5.67%。對于這樣的模型計算結果,是可以認為模型計算值和實驗測試值具有較強的一致性的,說明主動式冷梁工作模型在文中所列約束條件下具有較強的適用性。

3 結 語

在簡化條件下建立了誘導送風模型和表冷器換熱模型,在兩個模型的基礎上最終建立起了主動式冷梁工作模型。實驗測試了某主動式冷梁樣品的熱工特性,驗證了所建模型的準確性和適用性。

參考文獻:

[1]劉魁星,王夢蕾,田喆. 主動式冷梁空調系統適用性研究[J]. 建筑科學, 2013, 29(4): 73-78.

Liu K X, Wang M L, Tian Z. Study on applicability of active chilled beam air-conditioning system[J]. Building Science, 2013, 29(4): 73-78.(in Chinese)

[2] Stetiu C. Radiant cooling in US office buildings: towards eliminating the perception of climate-imposed barriers[D]. Berkeley: Energy and Resources Group, University of California, 1997.

[3] Stetiu C. Energy and peak power savings potential of radiant cooling systems in US commercial buildings [J]. Energy and Buildings, 1999,30(2): 127-138.

[4] Mumma S A. Dedicated outdoor air in parallel with chilled ceiling system [J]. Engineered Systems, 2001, 18(11): 56-66.

[5] Chowdhury A A, Rasul M G, Khan M M K. Thermal comfort analysis and simulation for various low-energy cooling technologies applied to an office building in a subtropical climate [J]. Applied Energy, 2008, 85(6): 449-462.

[6] Fong K F, Chow T T, Lee C K, et al. Solar hybrid cooling system for high-tech offices in subtropical climate-Radiant cooling by absorption refrigeration and desiccant dehumidification [J]. Energy Conversion and Management, 2011, 52(8/9): 2883-2894.

[7] Setty B S. Application issues for chilled beams technologies[J]. Ashrae Transactions, 2011,117(1): 494-501.

[8] Stein J, Taylor S T. VAV reheat versus active chilled beams DOAS[J]. Ashrae Journal, 2013(5): 18-32.

[9] 梁高林,劉振全,馬小禮. 低溫送風系統末端裝置誘導器的研究及性能評價[J]. 潔凈與空調技術,2006(3):12-14.

Liang G L, Liu Z Q, Ma X L. Study and performance evaluation of induction-unit of cold air distribution system [J].Contamination Control Air-Conditioning Technology,2006(3):12-14.(in Chinese)

[10] 張智力,張旭,張恩澤. 噴射型誘導風口誘導比的實驗研究[J]. 暖通空調,2008,38(2):62-64.

Zhang Z L,Zhang X, Zhang E Z. Experiment of induction ratio of the diffuser with nozzles [J]. Heating Ventilating Air Conditioning,2008,38(2):62-64.(in Chinese)

[11] 劉國強. 提高風機盤管系統冷凍供水溫度的節能評估[J]. 節能,2010,29(6):16-17.

Liu G Q. The energy-saving evaluation of improving supply water temperature fan coil system[J].Energy Conservation,2010,29(6):16-17.(in Chinese)

[12] 宋應乾,龍惟定,吳玉濤. 冷梁技術在辦公建筑中的應用與設計[J]. 暖通空調,2010,40(11):52-56.

Song Y Q, Long W D, Wu Y T. Application and design of chilled beams in office buildings [J].Heating Ventilating Air Conditioning, 2010, 40(11): 52-56.(in Chinese)

[13] 章戀. 主動式冷梁系統在智能辦公建筑中的應用探討[J].制冷與空調,2010,10(3):98-100.

Zhang L. Application discussion on the active cooling beam system used for intelligent office building[J]. Refrigeration and Air-Conditioning, 2010, 10(3): 98-100.(in Chinese)

[14] Memarzadeh F, Jiang J, Manning A. Numerical investigation on ventilation strategy for laboratories: An approach to control thermal comfort and air quality using active chilled beans[C]// Proceedings of Energy Sustainability Conference, Long Beach, California, USA: Solar Energy Division and Advanced Energy Systems Division, 2007: 409-416.

[15] 蔡增基,龍天渝.流體力學泵與風機[M]. 北京:中國建筑工業出版社,2009.

Cai Z J, Long T Y. Pump fan and fluid mechanics[M]. Beijing: China Architecture Building Press, 2009.(in Chinese)

[16] 章熙民,任澤霈,梅飛鳴. 傳熱學[M]. 北京:中國建筑工業出版社,2007.

Zhang X M, Ren Z P, Mei F M. Heat Transmission Science [M].Beijing: China Architecture Building Press, 2007.(in Chinese)

(編輯 胡 玲)

主站蜘蛛池模板: 国内黄色精品| 国产精品午夜福利麻豆| 久久精品aⅴ无码中文字幕| 国产网站在线看| 免费国产好深啊好涨好硬视频| 四虎在线观看视频高清无码| 亚洲精品无码抽插日韩| 手机精品福利在线观看| 国产精品天干天干在线观看 | 午夜影院a级片| 麻豆国产精品一二三在线观看| 亚洲综合天堂网| 欧美人在线一区二区三区| 亚洲无卡视频| 成人在线不卡视频| 久久人体视频| 久久久久国产一区二区| 婷婷99视频精品全部在线观看| 在线看片免费人成视久网下载| 很黄的网站在线观看| 色偷偷一区二区三区| 国产精品七七在线播放| 日本一区高清| 国产精品香蕉| 亚洲成人一区二区三区| 免费一级毛片不卡在线播放 | 一级毛片免费播放视频| 亚洲专区一区二区在线观看| 欧美日韩导航| 九九线精品视频在线观看| 激情六月丁香婷婷四房播| 91久久青青草原精品国产| 午夜限制老子影院888| 女人毛片a级大学毛片免费| 一级毛片无毒不卡直接观看| av一区二区人妻无码| 国产成人无码播放| 国产麻豆永久视频| 日韩毛片免费| 欧美在线三级| 国内毛片视频| 国产精品一区二区国产主播| 夜夜拍夜夜爽| 久久人搡人人玩人妻精品| 亚洲三级a| 欧美色视频网站| 欧美yw精品日本国产精品| 在线人成精品免费视频| 亚洲成年人片| 色视频久久| 欧美三级自拍| 国产成人精品三级| 国产a v无码专区亚洲av| 2021精品国产自在现线看| 精品国产香蕉在线播出| 国产女人18毛片水真多1| 色色中文字幕| 亚欧乱色视频网站大全| 丁香婷婷综合激情| 91精品专区国产盗摄| 国产亚洲欧美另类一区二区| 精品一区二区三区四区五区| 国产免费怡红院视频| 久久国产乱子| 精品人妻一区二区三区蜜桃AⅤ| 制服丝袜无码每日更新| 中文字幕啪啪| 青青久久91| 亚洲国产av无码综合原创国产| 成人小视频网| 91在线播放国产| 国产成人精品18| 国产精品黑色丝袜的老师| 久草视频中文| 国产精品一区二区久久精品无码| 久久99国产视频| 日本一区中文字幕最新在线| 色吊丝av中文字幕| 国产乱论视频| 999国内精品久久免费视频| 美女一区二区在线观看| 一级毛片无毒不卡直接观看|