摘 要:提出中央空調能效管理控制的方案,大大節省了有效的能源。選用飛利浦公司帶有I2C總線的單片機P87LPC764,溫度信號由TC1047A溫度傳感器采集后由模/數轉換器TLC0834轉換成數字信號,通過串行數據(SDA和串行時鐘(SCL二線傳入單片機。單片機進行數據分析、整理后把輸出信號傳輸至顯示模塊LCD621和數/模轉換器TLC5615進行顯示和控制變頻器,從而達到了調節電機功率、節能的目的。
關鍵詞:P87LPC764單片機;中央空調;節能;溫度控制
Efficiency′s Control System of Central Air-conditioning Based on SCM P87LPC764
HANG Jiatian1,LI Qiang1,YAN hengguo1,JIA Yajun2
(1.Ministry of Education ey Laboratory of Photoelectricity Gas-oil Logging and Detecting,Xi′an Shiyou University,Xi′an,710065,China;
2.China Petroleum Yumen Oilfield Operating Company,Yumen,735200,China
Abstract:Program of management of the energy efficiency of the central air-conditioning is proposed,it greatly saves effective energy.The system has used a Philips′s Microcontroller P87LPC764,which has a I2C bus.The temperature signal collected by the TC1047A temperature sensor will be converted into digital signals by the ADC TLC0834 and through Serial Data (SDA and the Serial Clock (SCL second-lines the digital signals will be imported SCM.After the input signal has been analyzed and finished by SCM,the output signal will be transmitted to display module LCD621 and digital to analog TLC5615 for display and control of inverter,so as to regulate the electromotor′s power and save the energy.
eywords:P87LPC764 SCM;central air-conditioning;energy saving;temperature control
1 引 言
中央空調系統主要由制冷機、冷卻水循環系統、冷凍水循環系統,風機盤管系統和散熱水塔組成。制冷機通過壓縮機將制冷劑壓縮成液態后送蒸發器中與冷凍水進行熱交換,將冷凍水制冷,冷凍水泵將冷凍水送到各風機風口的冷卻盤管中,由風機吹送冷風達到降溫的目的。
在系統中,冷動泵、冷卻泵、水塔風扇變頻器采用開環控制,由維護人員根據季節不同和負荷的變化進行調節,在每一個房間內都安裝熱交換器和循環風機,通過控制風機的轉速來改變熱交換量的大小,達到調節房間溫度的目地。
常見的控制方法是按“高、中、低、關”分檔模式控制,其缺點是房間的溫度需要手動調節,各種環境因素的變化常常會使人感到不適。風機轉速控制方案,采用變頻器調速控制,有效地解決了上述問題,達到了室內溫度自動調節的目的,大大的節省了能源。
3 中央空調能效管理系統性能特點
中央空調能效管理系統主要有以下特點:
(1 使用電源為220 VAC,功耗小于5 W;……p>